The FCPS-24S6C is a remote power supply with a battery charger.
The FCPS-24S6C may be connected to any 12 or 24-volt fire alarm control panel (FACP) or used as a stand-alone supply.
Primary applications include notification appliance (bell) circuit (NAC) expansion (to support ADA requirements and NAC synchronization) or auxiliary power to support 24-volt system accessories.
The FCPS-24S6C provides regulated and filtered 24 VDC power to four notification appliance circuits. The four outputs may be configured as all non-resettable, all resettable, or two nonresettable and two resettable.
Features & Benefits:
Operates as a “sync-follower” or as a “sync-generator”
Contains two fully-isolated input/control circuits
Four Class B (Style Y) or four Class A (Style Z, with ZNAC-4 module) NACs.
Compatible with coded inputs; signals passed through
Fully regulated and filtered power output - optimal for powering four-wire smoke detectors, annunciators, and other system peripherals requiring regulated/filtered power.